Interface Management Function
The LCD display records UPS operating status and parameter
information in real time, facilitating user management
High Environmental Adaptability Function
Circuit boards are housed in a fully enclosed space with triple-proof (dustproof, moisture-proof, corrosion-proof) coating, making them suitable for harsh environments such as tunnels and plazas.
Network Monitoring Function
Via RS232/RS485 communication interfaces and SNMP network adapters, combined with UPS intelligent monitoring software, the system communicates with computers. All UPS parameters are clearly displayed on the interface.
Product Features
True Dual Conversion Technology
LCD Screen Auto-Rotation (Only for 10K-20K Models)
DSP Technology Ensures Performance
Output Power Factor of 1.0
Power Factor Correction
50Hz/60Hz Frequency Converter Mode
Energy-Saving ECO Mode
Emergency Power Off (EPO) Function
Generator Compatibility & Dual Input Support
3-Stage Charging Design Optimizes Battery Performance
Adjustable Battery Quantity for Extended Runtime
Shared Battery Group Support
Optional Isolation Transformer & Parallel Operation
Multiple Communication Options: SNMP+USB+RS232
Maintenance Bypass & Walk-in Power Function
PARAMETERS
Model |
HR33-10KL |
HR33-15KL |
HR33-20KL |
HR33-30KL |
HR33-40KL |
HR33-60KL |
Capacity |
10kVA/10kW |
15kVA/15kW |
20kVA/20kW |
30kVA/30kW |
40kVA/40kW |
60kVA/60kW |
Input |
Input Voltage |
3×380VAC (3PH+N) |
Voltage Range |
190-520VAC (3-phase) at 50% load; 305-478VAC (3-phase) at 100% load |
Frequency Range |
46-54Hz or 56-64Hz |
Power Factor |
>0.99 @ 100% load |
Output |
Output Voltage |
3×360VAC/380VAC/400VAC/415VAC (3-phase+N) |
Voltage Stability (Battery Mode) |
±1% |
Frequency Range (Synchronization Range) |
46-54Hz @50Hz system; 56-64Hz @60Hz system |
Frequency Range (Battery Mode) |
50±0.1Hz or 60±0.1Hz |
Crest Factor |
3:1 (max) |
THD |
≤2% (resistive load); ≤5% (non-resistive load) |
Transfer Time |
Line to Battery: 0ms |
Inverter to Bypass: 0ms |
Waveform (Battery Mode) |
Pure Sine Wave |
Efficiency |
Line Mode |
95.50% |
Battery Mode |
94.50% |
ECO Mode |
98.50% |
/ |
Battery |
Extended Runtime Model |
|
Battery Type |
Depends on supplier |
Quantity |
16-20 (adjustable, default 16) |
32-40 cells |
32-40 cells (adjustable) |
Charging Voltage |
±13.65V×N (N=8-10) |
±13.65V×N (N=16-20) |
±13.65V×N±1% (N=16-20) |
Max Charging Current |
1A-12A (adjustable) |
1A-16A (adjustable) |
1A-18A (adjustable) |
Display |
LCD |
System status, load level, battery capacity, line mode, battery mode, bypass mode, fault indication, input/output voltage |
Overload Capacity |
Line Mode |
100-110%: 60 min; 110-125%: 10 min; 125-150%: 1 min; >150%: immediate protection |
Battery Mode |
100-110%: 60 min; 110-125%: 10 min; 125-150%: 1 min; >150%: immediate protection |
Physical Specifications |
Extended Runtime Model |
|
Dimensions (D×W×H, mm) |
680×458×133 |
797×438×170 |
Net Weight (kg) |
27 |
30 |
30 |
34 |
40 |
45 |
Operating Environment |
Temperature & Humidity |
0-95% RH, 0-40°C (non-condensing) |
Noise |
<60 dB @1m |
<65 dB @1m |
<70 dB @1m |
Control & Management |
Smart RS-232/USB |
Compatible with Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, and Mac |
Optional SNMP |
Supports SNMP and network management for power monitoring |